Hot insulation saves energy. Cold insulation prevents the system destroying itself — and the vapour barrier is the part that decides which happens.

Insulation looks like a finishing trade and behaves like a process one. On hot systems it controls energy loss and surface temperature; on cold systems it controls condensation, and a defect there causes corrosion under insulation that is invisible until the cladding comes off.

Cold insulation and the vapour barrier

On a chilled or refrigerated system the insulation is not the critical component — the vapour barrier is. Warm humid air carries moisture toward the cold surface, and any interruption in the barrier lets it condense inside the insulation, where it stays. The result is saturated insulation, no thermal performance and corrosion under insulation on the pipe beneath.

  • Continuous vapour barrier across the full system, including supports
  • Insulated pipe supports so the barrier is not pierced at every hanger
  • Vapour stops at intervals and at terminations to limit any ingress
  • Sealed penetrations at valves, flanges and instruments
  • Multi-layer construction with staggered joints on thicker applications

Hot insulation

  • Pipework, vessel, tank and equipment insulation
  • Personnel protection to hot surfaces within reach
  • Removable and reusable covers for valves and flanges requiring access
  • Expansion provision on hot systems that move
  • Heat trace accommodation where fitted

Materials

  • Mineral wool and rockwool for hot service
  • Closed-cell phenolic, PIR and elastomeric for cold service
  • Closed-cell spray polyurethane foam for tanks and irregular geometry
  • XPS rigid board where compressive strength is required
  • Calcium silicate for high-temperature applications
  • Acoustic insulation for noise attenuation

Finishing

  • Aluminium and stainless steel metal cladding, formed and banded
  • Weatherproofing and mastic sealing at joints and terminations
  • Lagging, canvas and coating finishes where cladding is not specified
  • Identification and flow marking
Corrosion under insulation: where existing insulation is removed, the substrate condition should be assessed before re-insulating. Re-cladding over a corroding surface conceals the problem for several more years.

Standards we work to

  • BS 5422
  • BS 5970
  • ASTM C547
  • ASTM C534
  • EN ISO 12241
  • ASTM C1136

Common questions

What clients ask before awarding

Why is cold insulation harder than hot?
Because it has to stop vapour as well as heat. Any interruption in the vapour barrier lets humid air reach the cold surface and condense inside the insulation, where it saturates the material and corrodes the pipe underneath.
What causes corrosion under insulation?
Water held against the substrate — from a vapour barrier defect, a cladding joint that leaks, or a penetration that was never sealed. It progresses unseen because the cladding hides it, which is why substrate condition should be checked whenever insulation is removed.
Do you supply removable covers?
Yes. Valves, flanges and instruments that need regular access are better served by removable and reusable covers than by insulation that is destroyed and rebuilt at every intervention.

Send us the drawings. We will tell you what it takes.

BOQ, isometrics, specifications or a full tender package. Acknowledged within one working day, with the machine schedule and programme in the offer.